Maxgeek 3062322 Generator Speed Controller Diesel Genset Speed Governor Speed Control Module Board

Availability: In stock, usually dispatched in 1 business day

  • Price:$43.04
  • Price in reward points: 430 Reward Points: 4
  • Quantity 3+ units 10+ units 30+ units 50+ units More
    Price /Unit $42.18 $41.32 $40.03 $38.31 Contact US
Quantity:

Maxgeek 3062322 Generator Speed Controller Diesel Genset Speed Governor Speed Control Module Board

Description:

The speed controller is a design with full electrical closed-loop path control function, which can
control generator perfectly when connecting with the matched actuator in EFC system, as it can
control the engine speed rapidly and accurately once getting instantaneous loading change.

Specification:
Electric Parameter:
RPM Stability: <±0.25%
Speed Range: 1KHz ~ 6.5KHz
Thermal Stability: Max ±0.7%
IDLE Regulation: 260 ±20Hz
DROOP Regulation: Minimum 15Hz ±6Hz/ 1Amp; Maximum: 400Hz ±75Hz/1 Amp
External Speed Regulation: ±200Hz (with 1KΩ connected)
AUX Input Sensitivity: 148Hz/1V, ±10Hz
Impedance: 1MΩ

Environment:
Working Temperature: -40 ~ 85℃
Working Humidity Range: Maximum 95%
Storing Temperature: -55 ~ 92℃
Shocking: 20-100Hz 500mm/Sec.

Input Power Supply:
Voltage: 12V or 24V
Grounding Pole: Negative pole
Power Supply: 40mA
Actuator Continuous Current: Minimum 1A, Maximum 4.5A
MPU Signal: 2 ~ 120V RMS

Note: Above mentioned parameters are tested with a 3800Hz working frequency.

Installation:
-Please use anti-slid self-lock screw to install after making hold in the suitable places according to the following data.
-The distance between the center and four hole is 135mm*102mm, the diameter of the hole is 5.5mm.

Terminals' introduction is as below:
Speed controller
No.1, No.2 terminals: 1 is DC positive, 2 is DC negative
No.3, No.4 terminals are the output connector of Actuator
No.5, No.6 terminals are the input connections of MPU
No.7, No.8, No.9 terminals are external RPM fine tuning
No.10 is the connector of idle-speed switch
No.11 terminal is free connector

Adjustment:
The speed controllers shall be adjusted before sending out from factory, but it can be adjusted
slightly again during the operating according to different engine models, the operation is as below:
1. adjust to the initial position:
if wrong operation is made during the operation that the potentiometers adjustment is in a mess
then please adjust as the instruction below:
A. stop engine and switch off the power of speed controller;
B. please adjust IDLE SPEED to middle point(turning around 20 circles. Firstly use inverted direction to the bottom then turn around 10 circles in clockwise direction);
C. please adjust RUN SPEED to middle point (turning around 20 circles. Firstly use inverted direction to the bottom then turn around 10 circles in clockwise direction);
D. please adjust GAIN to 20%~50%(turning around 1 circle);
E.please adjust DROOP to 0.

IDLE:
Usually the IDLE speed is 600-800 RMP per min, if turning IDLE in clockwise direction,the
RPM will be increased; if turning IDLE in inverted direction, the RPM will be decreased.

RUN:
Usually the speed of idle load is 1515RPM per min(50.5Hz), rated load is 1500RPM per min (50.0Hz). if turning RUN in clockwise direction,the RPM will be increased; if turning RUN in inverted direction, the RPM will be decreased.

GAIN:
The running speed of engine responses rapidly when turning GAIN in clockwise direction,
the running speed of engine is stable when turning GAIN in inverted direction, the places are in
No.5-No.7.on the occasion of idle load, please adjust GAIN in clockwise direction slightly till the
running speed is up, then ajust GAIN in inverted direction slightly till the speed is stable.

DROOP:
The function of DROOP: when the load is increased, then running speed of engine will be decreased. If turning DROOP in clockwise direction, then the running speed's drop-out value will be increased; if turning DROOP in inverted direction, then the running speed's drop-out value will be decreased.

Package List:
1 x Generator Speed Controller